Sale!

Generac 100 Amp 24-circuit Load Center Automatic Transfer Switch SE ATS – NEMA 1 UL (not CUL)

Original price was: $539.00.Current price is: $107.80.

SKU: RXG24SHA1 Category: Tag:

Description

A 24-circuit distribution interior isolates critical branch circuits during utility electrical dropouts. The Generac 100 Amp 24-circuit Load center switch transfers emergency power from incoming utility lines to backup generators. This 100 Amp indoor NEMA 1 service-rated switch protects maintenance shop lights, lift circuits, and battery bays. It cannot withstand wet outdoor weather exposures.

The NEMA 1 cold-rolled steel cabinet mounts flush or surface-mount against interior drywall and studs. A factory-installed 24-circuit breaker interior accepts standard Siemens or Square D type circuit breakers. Solid copper internal bussing directs 100 Amp split-phase 120/240-volt power without heat distortion. Heavy electro-mechanical transfer arms cycle between line and generator power via high-torque solenoid drives. Mechanical interlocking brackets prevent simultaneous utility grid and standby generator phase connections.

Load Center Contactor Hardware

Interior fleet service buildings depend on subpanel isolation to keep vehicle repair bays operational during utility blackouts. This load center switch organizes branch distribution within one compact chassis.

  • 24-circuit integrated breaker interior organizes isolated branch circuits in shop buildings
  • 100 Amp main contactor handles full subpanel loads without thermal breaker trips
  • 120/240 split-phase electrical architecture feeds standard commercial tool shop wiring
  • NEMA 1 sheet steel indoor enclosure mounts between sixteen-inch center wall studs
  • Service rated design incorporates utility disconnect breakers inside the cabinet enclosure
  • Solenoid transfer mechanism throws double-pole contacts in under 200 milliseconds
  • Mechanical interlock linkage prevents backfeeding power into municipal power grids

Electrical Bench Stress Metrics

Load bench diagnostic runs apply 100 Amp continuous electrical loads across all 24 subpanel circuits. Terminal lug temperatures stabilize at 42 degrees Fahrenheit above shop ambient temperature during four-hour runs. Contact throw sound levels hit 73 dBA at three feet during solenoid engagement cycles. Switching latency clocks at 180 milliseconds following auxiliary generator voltage stabilization. Dielectric breakdown testing confirms the internal steel chassis and insulation barriers withstand 2200-volt high-potential electrical surges without arc tracking.

Indoor Setup Application Boundaries

Electricians wire branch circuits straight to the interior breaker bussing inside climate-controlled commercial buildings. Operators observe breaker status through the hinged metal access door. Do not install this NEMA 1 cabinet outdoors, inside unheated damp wash bays, or in chemical spray storage areas.

  • Branch breaker wire screw terminals require torque checks to 35 inch-pounds once each year
  • Main contactor silver alloy surfaces require visual inspection for carbon burns every year
  • Enclosure grounding bonding screws require torque verification to 25 inch-pounds every season

Warranty Terms Crate Contents

Generac protects this RXG24SHA1 load center switch with a 5-Year commercial limited warranty. The package contains the 100 Amp 24-circuit indoor transfer switch cabinet unit, circuit identification labels, mounting hardware screws, enclosure door key, and complete electrical wiring guide.